Analysis of Positive and Negative Lightning Impulse Discharge Characteristics in Long Air Gaps
Year: 2025
Type: article
Abstract: Lightning is a common cause of failure in high-voltage transmission lines. This paper uses physical models of positive and negative discharges to analyze the differences in discharge characteristics between rod–plane and conductor–tower gaps. It also explores the influence of different tower structures on the discharge process. The simulation results show that negative leaders develop in a stepped manner and progress rapidly, while positive leaders develop continuously and progress more slowly. Under the same lightning impulse voltage level, negative discharges exhibit higher breakdown voltages. The development speed of positive discharges is mainly influenced by the applied voltage, while negative discharges are less affected by the applied voltage. For the same gap distance, the 50% breakdown voltages in the conductor–tower model are significantly higher than those in the rod–plane model for both polarities. Additionally, under shorter gap conditions, negative discharges may not show distinct stepped characteristics. This study provides theoretical guidance and practical references for lightning protection design and engineering applications in high-voltage transmission lines.
Source: Energies
DOI: 10.3390/en18215746
Authors: Ruifeng Zhu, Jianwen Nie, Yun Zhang, Zhenxin Zhong, Xinru Li, Yuxi Dong, Jiachen Gao
Language: English
Subfield: Astronomy and Astrophysics
Field: Physics and Astronomy
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,137
Funder: China Southern Power Grid
Award: G31255226
OpenAlex ID: W4415819115