Year: 2025
Type: article
Abstract: The large-scale integration of renewable energy grid-connected converters into the grid has given rise to many broadband oscillation accidents, primarily due to impedance mismatching with the grid. Consequently, accurate measurement of both the grid-connected converter and the grid impedance is a prerequisite for system stability assessment. However, conventional impedance measurement methods are constrained by the breakdown voltage of semiconductor switches, thus rendering them unsuitable for high-voltage, high-capacity applications. This paper aims to enable impedance measurement in large-capacity, high-voltage applications by presenting a newly developed method that overcomes the voltage limitations of conventional approaches. First, a cascaded H-bridge (CHB) topology is adopted to fulfill the impedance measurement requirements in large-capacity, high-voltage renewable energy station applications. Subsequently, a quasi-proportional-resonant (PR) controlled perturbation injection strategy is proposed to achieve rapid current injection across the 10–1000 Hz frequency range. Finally, the effectiveness and accuracy of the proposed impedance measurement method in capturing harmonic impedance are demonstrated through a hardware-in-the-loop (HIL) experiment conducted on an RTDS platform.
Source: Electronics
Authors: Ze Wei, Tao Xu, Jianan Mu, Lin Cheng, Ning Chen, Luming Ge, Xiong Du, Guoning Wang
Language: English
Topic: Power Quality and Harmonics
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $2,896
Funder: State Grid Corporation of China
OpenAlex ID: W4417042471