Estimation of the Nigerian Power System Electromechanical Modes using FDR Measurements
Year: 2010
Type: conference-paper
Abstract: This paper reports on an ongoing research effort between researchers in North America and Africa on the study of the dynamics of loosely regulated and rapidly growing power systems, with focus on the Nigerian power network. A description of the implementation of Virginia Tech’s FDR (Frequency Disturbance Recorder) at Bauchi, Nigeria is provided. We discuss the nature of the frequency dynamics observed throughout multiple hours of a day in Nigeria and other power systems. To cater to the loosely regulated nature of the system frequency in Nigeria, we propose an appropriate method for signal conditioning which prepares the data for ambient analysis. Parametric and nonparametric block processing techniques are applied to prolonged frequency recordings ranging from 8 to 19 hours, and estimates of modal frequencies and damping are obtained by computing power spectrum densities and applying a mode meter algorithm to the ambient data. The estimated modes from ambient analysis are in agreement with other studies based on power system models.
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W58404436