Optimisation of passive system components to minimise DC circuit breaker stresses in multi-terminal HVDC systems
Year: 2015
Type: conference-paper
Abstract: HVDC circuit breaker designs have commonly included additional series inductance to reduce the rate of rise of current during the initial transient period after a fault occurs, minimising the peak current stress that the circuit breaker must endure. A method of approximating the peak fault current and energy dissipation in a circuit breaker is developed, through circuit analysis of a multi-level converter (MMC) under fault conditions. These approximations are validated against simulation results for an 800kV MMC system
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W594583263