Supression Method of Source Voltage Fluctuation Utilizing Reactive Power Compensation on Ac Electric Railway
Year: 1993
Type: article
Abstract: In the case of the newly a.c. electrified railway projects, it is likely that a strong power supply may not be available locally. Further, re-generative braking has recently been applied to electric rolling stock. The result is poor when a 3-phase-to-2-phase transformer is used to reduce the unbalanced power. So, in some cases reactive power compensation may be found more favourable than a 3-phase-to-2-phase transformer. This paper describes a theoretical study and results of tests on a small scale model which utilizes reactive power compensation on primary-side of a modified wood-bridge connected transformer. On a.c. electrified railroad, in which two single-phase loads change independently of each other, rective power compensation capacity differs for each of the 3-phases. Therefore, reactive power capacity has to be controlled separately for each phase.