The influence of air flow on current interruption with air-break HV disconnectors
Year: 2011
Type: conference-paper
Abstract: The application of forced air flow is one of the possible approaches for quenching the during current interruption with air-break HV disconnectors. In the present paper, a series of experiments is presented to investigate the influence of the air flow on the small capacitive interruption with current up to 7.5A at 90kV phase voltage. Experimental data analysis shows that the arcing duration reduced 40%-50%, compared to interruption without air flow. This is because the re-strike voltage across the gap between the main contacts of the disconnector is increasing nearly linearly with increasing air gap distance with the assistance of the air flow. The re-strike frequency and the time derivative di/dt at current zero with air flow are much higher than that without air flow. Moreover, images show that there are two different modes: arc and arc. The obtained results reveal that application of air flow may convert thermal interruption mode to dielectric interruption mode, increases the dielectric strength of the air gap, and increases the interruptible di/dt with about a factor of 20. The mechanisms are discussed causing it to be an effective method to improve the interrupting capability of the air break disconnector.
Source: TU/e Research Portal
Institution: Eindhoven University of Technology
Language: English
Topic: Vacuum and Plasma Arcs
Subfield: Atomic and Molecular Physics, and Optics
Field: Physics and Astronomy
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W635530777