Abstract: This paper discusses recent and ongoing switch testing for fusion devices. The first part describes testing for the TFTR ohmic-heating circuit. In this set of tests, which simulated the stresses produced during a plasma initiation pulse, circuit breakers were required to interrupt a current of 24 kA with an associated recovery voltage of 25 kV. Two interrupter systems were tested for over 1000 operations each, and both appear to satisfy TFTR requirements. The second part discusses hybrid-switch development for superconducting coil protection. These switching systems must be capable of carrying large currents on a continuous basis as well as performing interruption duties. The third part presents preliminary results on an early-counterpulse technique applied to vacuum interrupters. Implementation of this technique has resulted in large increases in interruptible current as well as a marked reduction in contact erosion. (MOW)