Work

Integrating PV Systems with Non-Standard Grid Voltages

Year: 2025
Type: conference-paper
Abstract: Installing grid-connected photovoltaic (PV) systems is challenging in regions with nonstandard grid voltages, as PV inverters are designed for standard levels. To overcome this limitation, transformers can be used, but their inrush current often trips inverter protection. This paper explores this issue, emphasizing the need for specially designed low-induction transformers.
Authors: Badri, José Antonio, Riba, Jordi-Roger, Garcia, Antoni, Marzabal, Albert, Trujillo, Santi
Language: English
Field: Energy
Open Access status: green
OpenAlex ID: W6890064427
FWCI:
Cites:
Cited by: