Year: 2024
Type: article
Abstract: This paper presents the results of research on improving the protection, automation and monitoring systems of power transformers (PT) in 6-35 kV distribution networks. The authors have developed improved algorithms for differential and distance protection of a transformer based on measuring voltage and current synchrophasors, proposed additional criteria for blocking protection in the event of a magnetization inrush current (MIC), and considered the functions of the transformer monitoring and automation system based on synchrophasor technology.
Authors: Sergey Piskunov, Alexey Mokeev, Dmitry Ulyanov