Abstract: Geomagnetic disturbances (GMD) affect power systems by causing transformer saturation.The primary impacts of transformer saturation are increased harmonic current injections and var losses, which may lead to loss of high-voltage transformers and/or voltage collapse.The investigation of GMD risks and mitigation strategies requires accurate modeling of a GMD.Benchmarks for such studies are rare.This paper proposes an Electromagnetic Transient (EMT)-type benchmark for GMD studies which is based on a modified version of the IEEE 39-bus benchmark; it includes several features found in a real network that are relevant to GMD studies such as: different voltage levels; multiple transmission lines with different orientations; two-and three-winding transformers; transformer models with on-load-tap-changer functionality and realistic nonlinear magnetization branch models for harmonic analysis and var consumption studies; synchronous generator models with realistic saturation data and over-excitation limiter functionality for voltage regulation and voltage collapse studies; reactive power equipment, LV transformers and feeders; and a generic model of geoelectric field.