Energiesektoren-übergreifende Lastspitzenreduktion mit elektrischen und thermischen Energiespeichern
Year: 2021
Type: dissertation
Abstract: Peak loads cause high and unpredictable loads on the power grids and increased transmission losses in the distribution networks. The compensation of short-term high electrical energy demand also requires inefficient and expensive peak load power plants as well as oversized grid components. In order to achieve an electrical energy demand by larger consumers that is as even as possible, the grid operators set financial incentives. These include a demand rate, which depends on the maximum power value during the billing period. A reduction of the peak loads thus opens up high savings potentials for industrial and commercial companies. The methodology and application of peak shaving across different energy sectors as well as the influence on the energy system are investigated in the present thesis. In addition to electrical energy storage systems, thermal plants are also used for peak shaving to increase the reduction potential, which is different from existing literature. This includes heat and cold water supply systems, which are often part of industrial energy systems. The thesis focuses on a combined heat and power plant with heat energy storage and a cooling plant with cold thermal energy storage. However, the approach can be transferred to similar components. The energy storages provide the flexibility, which is needed for the additional usage of the plants for peak shaving. Data-based models are used to represent the behavior of the components (plants, energy storages and peripherals) in simulations, which enable a non-invasive investigation of the cross-sectorial peak shaving. Peak shaving with the plants and storages requires algorithms and operational strategies for the detection of relevant peak loads, calculation of setpoints as well as for the operation in normal and peak modes. In comparison to the state of the art, relevant characteristics of the components (e.g. startup procedures) are fully taken into account. The methods can be transferred to fields, which were not considered in the thesis, e.g., compressed air and air reservoir. The overall objective is to comply with a power limit, which can be varied over time to apply for individual network fees like atypical network usage. The models and operational strategies are merged in an expandable and flexible simulation environment. This is used to present and investigate various scenarios as well as to optimize components and parameters. The components are linked dynamically within the program via a netlist, which greatly simplifies extensions and thus enables extensive investigations. The simulations show that a battery is necessary to observe a predefined load limit, as it can be operated very dynamically and provides a continuously variable output power. In the first scenario, a battery system is considered. A peak shaving potential of about 10 % is determined for the parameters of a reference system, which shows load peaks in the range of one Megawatt. This leads to a payback time of less than five years. With the additional consideration of a combined heat and power plant with thermal energy storage this value increases to approx. 18 %. A combination with a cold thermal energy storage shows a potential of 21 %. This leads to an annual saving of 21 thousand euros assuming a demand rate of 100 euros per kilowatt. A second annual data set from the reference system confirms a similar impact of the measures on total savings. If the normal operation of the CHP is also taken into account, the savings are in the range of 139 thousand euros per year, which results in a payback period of less than three years. As the absolute results are strongly dependent on the plant dimensions, a method for the calculation of the reduction potential with variation of nominal power and capacity of the plants and storages is shown and applied for numerous parameter sets. The algorithms and operational strategies were implemented into a reference system. It provides measurements, which are used for validation of the simulations. Compared to the measurements, only minor differences with a mean absolute error of four kilowatts occur for the resulting transformer power. The present thesis thus provides an approach for planning and realization of the successful cross-sectorial peak shaving. The thesis also illustrates the exemplary application of component dimensioning, optimization of algorithm parameters and implementation of operation strategies in a real system.
Author: Lange, Christopher
Institution: Friedrich-Alexander-Universität Erlangen-Nürnberg
Language: German
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Keywords: peak shaving, thermal energy storage, cold energy storage, combined heat and power plant, cooling plant, battery energy storage, demand rate, demand-side management, operational strategy, start-up process, industrial energy systems, compressed air energy storage, air reservoir, simulation environment
Open Access status: green
OpenAlex ID: W7037645589