Design of a low-frequency impedance measurement system applicable to LV grids in live conditions
Year: 2025
Type: conference-paper
Abstract: The design of an impedance measurement system isdiscussed for application in low-voltage power grids in operation,addressing the presence of the grid voltage. A shunt injectionarrangement is preferred, relying then on the measurement ofthe port voltage and current. A Twin-T passive filter is designedto buffer the isolating injecting transformer, suppressing the50 Hz fundamental and avoiding excessive magnetizing currentand voltage the signal generator connected to the secondaryside. Before construction, the system has been simulated andparameters values optimized, showing good performance evenwith very large-power grids with impedance Zg of tens of mΩ.Zg estimate uncertainty is < 1 % at coverage factor k = 1.
Author: Mariscotti, Andrea
Institution: University of Genoa
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
Award: G8954558844
OpenAlex ID: W7085841380
FWCI:
Cites:
Cited by: