Experimental Verification of a Method for Improving the Efficiency of an Evaporative Tower Using IEC
Year: 2026
Type: article
Abstract: This paper analyses the impact of inlet air precooling on the efficiency and electricity consumption of an open-type evaporative cooling tower. An Indirect Evaporative Cooler (IEC) was used to reduce the inlet air temperature, and its influence on system efficiency was experimentally evaluated. Although IEC units and the Maisotsenko cycle are increasingly discussed in the literature, no research to date has considered their effect on evaporative tower efficiency under actual operating conditions. For this purpose, a test stand was constructed comprising an open cooling tower and an IEC unit. The system operated automatically for 2952 h, corresponding to a full cooling season in Poland. Two sets of data collected during cooling tower operation were analysed: without precooling (Stage I) and with precooling using IEC (Stage II). Measurements were recorded every 10 s. Additionally, tests were conducted at elevated thermal loads and peak ambient temperatures. The comparative analysis concluded that air precooling using IEC reduced the cooling tower’s electricity consumption by approximately 15% and increased the SCOP of the cooling tower by 30%. This demonstrates the significant potential of the proposed solution.
Source: Energies
DOI: 10.3390/en19020554
Authors: Bartosz Jagieła, Magdalena Jaremkiewicz
Institution: Cracow University of Technology
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,137
OpenAlex ID: W7125604226