Fault Location and Calibration of Multi-Terminal DC Ring Network Based on Traveling Wave Redundant Information
Year: 2026
Type: article
Abstract: Traditional single-ended traveling wave fault location is sensitive to velocity uncertainty, complex topologies, and variations in the equivalent impedance of converter stations. This paper proposes a fault distance calibration method based on the fusion of traveling wave redundant information and inverse weighting: multiple sets of initial distance estimates are formed using wave fronts arrival times measured at multiple terminals. These estimates are then calibrated through inverse weighting fusion according to the error sensitivity of each redundant observation, thereby suppressing errors caused by wave velocity deviations and structural inhomogeneities. Simulation verification using PSCAD/EMTDC for a four-terminal VSC-MTDC loop network demonstrates that this method reduces dependence on precise wave velocity measurements while enhancing the accuracy and robustness of DC loop network fault location.
Source: Eng—Advances in Engineering
DOI: 10.3390/eng7020089
Authors: Zewen Li, Wenxian Chen, Fangming Deng, Yuzhe Liu
Institution: East China Jiaotong University
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $1,448
OpenAlex ID: W7128974786
FWCI:
Cites:
Cited by:
Related to: