Individualization of personal space in hospital environment

Year: 2013
Type: dissertation
Abstract: VI possible hbExCr, lower metabolic thermal exergy rate and also lower exergy rates of exhalation and evaporation of sweat, radiation and convection.These values are lower than in conditions created with conventional system.Healing oriented conditions for patient do not present also comfortable conditions for healthcare worker and visitor.Therefore, active regulation of thermal comfort zone is developed in the doctoral dissertation.Designed LowEx system enables active regulation of thermal comfort zone with setting up optimal relation between mean radiant temperature and air temperature for every individual separately, without deterioration of thermal comfort of other users.In such way individualized climate is created; consequently, quicker recovery and shorter hospitalization are expected, as well as increased productivity of workers.Conventional system does not enable to do that.The measured energy use for space heating was by 11-27 % lower when using LowEx system than for conventional system.In case of cooling the measured energy use was by 30-73 % lower for LowEx system.At the end the overall harmonization of individual demands and needs for users is attained, required regulated demands for hospital environment are fulfilled and at the same time building energy use for H/C is minimized.