Impact of Fault-Induced Tripping of Sink-Area Renewable Energy Sources on Power System Voltage Stability

Year: 2026
Type: article
Abstract: Voltage stability assessment of a transmission interface is carried out by continuation power flow (CPF) using a fixed post-contingency operating condition. However, if legacy renewable energy sources (RESs) in the sink area are tripped during or following a fault, the actual post-fault operating point can differ from that assumed in the CPF study. This paper examines the effect of sink-area RES tripping on transmission interface voltage stability. The shift in the post-fault operating point caused by the loss of sink-area active power injection is explained using a two-bus equivalent, and the effect of reactive power support from connected RES on the transfer limit is also discussed. The proposed analysis is verified using a modified SAVNW test system in PSS/E. Two contingency scenarios were studied by applying a three-phase fault at the receiving-end bus and tripping one transmission interface line at fault clearing. The results show that sink-area RES tripping moves the post-fault operating point toward the nose point and reduces the voltage stability margin. The results also show that reactive power support from connected RES increases the transfer limit and leads to a larger margin. These effects should be considered in voltage stability assessment of transmission interfaces with legacy RES.