Impact of hybrid solar and wind distributed generators on transient stability of captive power systems
Year: 2026
Type: article
Abstract: This paper investigates the impact of solar and wind distributed generators on the transient stability of a 39-bus industrial power system. The system is analyzed under different configurations, including wind-only, solar-only, and hybrid DG integration. Critical Clearing Time (CCT), active power, and reactive power are used as performance metrics. The results show that DG integration improves system stability compared to the baseline case. Specifically, the CCT increases from 0.018 s (without DG) to 0.0248 s with wind DG, and up to 0.3168 s with solar DG. The hybrid configuration results in a CCT of 0.0297 s. These results indicate that solar DG provides the highest improvement in transient stability due to better voltage support characteristics. The study highlights the importance of DG type and placement in improving stability and provides insights for industrial power system design.
Source: Scientific Reports
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $2,690
OpenAlex ID: W7162071706
FWCI:
Cites:
Cited by:
Related to: