Work

Définition d'un profil de sollicitation typique d'une batterie pour la fourniture de la réserve primaire de fréquence

Year: 2026
Type: conference-abstract
Abstract: This work proposes a methodology for defining a standard duty profile for a battery used in primary reserve applications (Frequency Containment Reserve, FCR) on the electrical power grid. These profiles are built from RTE frequency data and a simulation algorithm of the storage system's operation. The objective is to use these profiles to assess the impact of FCR provision on the aging of lithium-ion batteries, particularly in the context of repurposing toward second-life stationary applications. The method relies on (i) preprocessing of frequency time series and detection of grid states (normal, alert, emergency), (ii) a power-frequency simulation incorporating state-of-charge (SoC) management strategies for the battery, (iii) the extraction of 29 monthly indicators reduced via Principal Component Analysis (PCA), and (iv) a k-means clustering into 2 clusters over 127 months. The resulting standard profile, lasting 720 hours (1 month), is intended for experimental aging tests of second-life LFP and NMC cells.
Source: HAL
Language: French
Open Access status: green
OpenAlex ID: W7212414543