Optimal Temperature Control in 5GDHC Networks using a Detailed Simulator

Year: 2025
Type: conference-paper
Abstract: 5th Generation District Heating and Cooling (5GDHC) networks provide both heating and cooling. They enable decarbonization of heating needs and provide resilience to an increasing cooling demand. The present study focuses on optimizing the primary temperature setpoint to minimize CO 2 emissions, which comes solely from electricity use by heat and hydraulic pumps. A reduced model is used for optimization, with parameters calibrated from a detailed simulator accounting for pipe thermal inertia, heat losses, and pressure drops. Various optimization methods (MILP, NLP) are then compared on the detailed simulator over a 15-day period, showing that optimization outperforms naive control strategies. CO 2 emissions are reduced by 1% in winter and up to 7% in summer, notably by anticipating and storing energy before CO 2 intensity peaks. The study also discusses the benefits of storage for such networks. INTRODUCTION Context Fifth-generation district heating and cooling (5GDHC) networks represent a revolutionary advancement in urban energy infrastructure, playing a pivotal role in the global transition towards sustainable and low-carbon energy systems. Unlike traditional district heating systems, which often rely on centralized heat production from fossil fuels, 5GDHC networks leverage local, renewable, and low-grade heat sources. These sources include solar thermal, geothermal, and waste heat from industrial processes or data centers. Recently, the International Energy Agency (IEA-DHC, 2024) has considered these 5GDHC networks as a subclass of fourth-generation networks, labeling them "Thermal Source Networks" (TSN). For consistency with related papers, the term 5GDHC is used here, although it is considered equivalent to TSN. The core innovation of 5GDHC lies in its ability to integrate both heating and cooling needs within a single, flexible network. This is achieved through low-temperature distribution systems that circulate water at nearambient temperatures, typically between 10°C and 40°C. This temperature range allows for the efficient use of heat pumps in buildings, which can upgrade low-grade heat for space heating or provide cooling. The three main advantages of 5GDHC networks are: • The local balancing of heat and cold. • Their ability to utilize heat sources at lower temperature. • The electrification of the heat demand, which reduces the greenhouse gas emissions of heating. However, the widespread adoption of 5GDHC faces several challenges, including the need for substantial initial investments, regulatory barriers, and the requirement for technological advancements in heat pump and storage technologies. This paper aims to determine the optimal network primary temperature that minimizes the cumulative greenhouse gas emissions of a 5GDHC network. State of the art Interest in 5GDHC systems has surged significantly over the past decade. Across Europe, Buffa et al. ( 2019) identified 40 operational systems, showcasing a variety of designs and operational principles. They developed a classification system for network types, considering factors such as the number of pipes, flow bidirectionality, energy flow, and heat sources. Building on this classification, Sommer et al. (2022) proposed three main categories of 5GDHC systems: • Classical Networks: These networks consist of a supply pipe and a return pipe, similar to older generation
Source: HAL
Language: English
Open Access status: green
OpenAlex ID: W7213859609
FWCI:
Cites:
Cited by:
Related to: 10