Year: 2026
Type: article
Abstract: High penetration of inverter-interfaced renewable generation reduces the equivalent inertia of power systems and increases the need for fast frequency support from power-electronic resources. Grid-forming (GFM) converters can provide virtual-inertia and droop responses, whereas grid-following (GFL) converters can contribute additional active power through frequency-dependent control but exhibit different synchronization and response dynamics. This paper develops a reduced-order model for coordinated frequency support of a GFM battery energy storage system (GFM-BESS) cluster and a GFL renewable energy source (GFL-RES) cluster. Particle swarm optimization is used to coordinate the virtual-inertia coefficient and the GFM/GFL active-power support gains. Three strategies, namely Conventional, GFM-only, and Proposed, are compared under a 10 MW load disturbance. Relative to Conventional control, the Proposed strategy reduces the maximum frequency deviation from 0.6084 Hz to 0.4556 Hz and the maximum RoCoF from 0.8331 Hz/s to 0.5188 Hz/s, corresponding to reductions of 25.1% and 37.7%, respectively. Compared with GFM-only control, it reduces the peak GFM support by 18.0% while the GFL cluster provides 2.366 MW of peak support. The results indicate that coordinated GFM/GFL control can improve transient frequency performance while distributing short-term support more effectively between converter clusters.
DOI: 10.61784/wjer3128
Institution: Guangdong Power Grid Company (China)
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: hybrid
OpenAlex ID: W7223255425