Transient Voltage Immunity of Grid-Following Converters: Assessment and Suppression of Post-Fault Temporary Overvoltage
Year: 2026
Type: article
Abstract: Grid-following converters (GFLCs) exhibit an inherent delay in responding to post-fault voltage variations due to measurement and control mode transition latency. Therefore, post-fault temporary overvoltage (TOV) may arise, making renewable power plants vulnerable to widespread cascading tripping. To address this issue, this paper reveals the underlying mechanism of TOV and enhances the TOV suppression capability of GFLCs. First, the TOV mechanism is elucidated through singular value analysis of the current division ratio derived from the equivalent impedance model. Thereafter, the inherent trade-off between the current tracking capability and TOV suppression performance of GFLCs is revealed. On this basis, a transient voltage immunity (TVI) index is proposed to analytically assess the transient voltage overlimit resilience capability of GFLCs. To enhance the TVI for TOV suppression, an adaptive voltage feedforward control scheme is proposed, where the current control performance and the small-signal stability are simultaneously satisfied. Finally, electromagnetic transient simulations based on PSCAD are conducted, and the results under various scenarios validate the effectiveness of the proposed method.
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green