Adjacent Heat Transfer Effects Can Bias Savings Estimates When Controlling Only Part of a Multi-Zone Building

Year: 2026
Type: preprint
Abstract: Field demonstrations of advanced heating, ventilation, and air-conditioning control often operate a few thermal zones within a larger building and report savings for those zones alone. A recent theorem showed that this practice overestimates whole-building savings, because heat drawn from the neighboring zones is paid for by their equipment and is not counted. The error grows with the thermal conductance between the controlled and uncontrolled zones, with how much colder the controlled zones run over the test, and with the price of the heat their neighbors supply. For one controlled zone with one neighbor, a single thermal price, and slowly changing prices, the relative error reduces to the ratio of two conductances, a screening number that can be evaluated from the two conductances before a demonstration begins. This paper tests how far that reduction can be taken. A two-story house with one thermal zone per floor is simulated over a 90-day heating season in West Lafayette, Indiana, with receding-horizon model predictive control on the first floor and setpoint control on the second, under four combinations of electricity tariff (time-of-use or flat) and heating plant (heat pump or electric resistance). The exact correction from the theorem recovers the true savings in every case, and the full theorem, evaluated from the controlled zone's temperatures, the prices, and the building parameters, reproduces the measured relative error in every case. The conductance ratio bounds that error from above in all four cases, tightly under a flat tariff, within 3%, and loosely under a time-of-use tariff, where most of the controller's savings come from shifting load through the thermal mass rather than from lowering the temperature.
Language: English
Open Access status: green
OpenAlex ID: W7226017681
Cites: 2
Cited by:
Related to: 10