Geothermal Snow-Melting for a Bridge Deck and Plaza: Snowfall Melt-Flux, Slab Heat and Direct-Use Flow Budgets

Year: 2026
Type: article
Abstract: This paper presents a computed design study of a geothermal energy system on a single stated operating principle: warm geothermal water circulated through tubing cast into a pavement slab delivers a computed heat flux at the surface sufficient to melt falling snow as fast as it accumulates — the slab is a heat exchanger whose upper face is the weather, and the design load is set by the snowfall rate, not by a thermostat. The system is a combined bridge deck and pedestrian plaza of 4,800 square metres in a climate with a design snowfall of 3.0 centimetres per hour of fresh snow at 110 kilograms per cubic metre and an ambient temperature of minus 7 degrees Celsius, supplied at 62 degrees Celsius and returned at 34 degrees Celsius. The design target is the design surface heat flux built up from the snowfall's melt and warm-up requirements with a stated loss factor, the total slab duty, and the geothermal flow and embedded pipe length the duty implies. The design surface flux is 463 watts per square metre, of which 319 watts per square metre is the snowfall's own melt and warm-up requirement; the slab duty is 2.22 megawatts, served by 18.9 kilograms per second through 19,200 metres of embedded pipe. The purpose throughout is civilian energy supply: electricity for grids and facilities, or heat for buildings, food production and industry. Nothing in the design is optimized for any other use, and the study has no targeting or weapon application. It is a computed study; every performance figure is simulated from the stated assumptions, not measured.
Language: English
Field: Energy
Open Access status: green
OpenAlex ID: W7228535549
FWCI:
Cites:
Cited by:
Related to: 10