False Transformer Pressure Trip and Failure of Automatic Bus Transfer: A Real Case Study of Incomer Loss and ATS Malfunction in a Petroleum Facility Substation
Year: 2026
Type: preprint
Abstract: This paper presents a real case study of a simultaneous protection and automatic transfer failure in substation of a petroleum facility in Egypt. On 12 March 2026 at 20:25, Transformer TR-A tripped on a transformer pressure trip indication via the RET620 protection relay, causing Incomer A of PMCC to go out of service and an under-voltage condition on the corresponding bus section. Although the bus coupler was in AUTO mode and Incomer B remained energized, the Automatic Transfer Scheme (ATS) failed to close the bus coupler automatically, resulting in load interruption and fan shutdown. Power was restored by manual closing of the bus coupler, after which Transformer TR-B supplied both bus sections. Post-event inspection revealed no internal transformer fault. Insulation resistance was 6.84 GΩ on the HV side and 6.76 GΩ on the LV side, and winding resistance values were within normal limits. No fresh oil leakage was observed at the Pressure Relief Valve (PRV). Burn marks and thermal damage were observed on the CT protection terminal block XA2 (XA2-1 to XA2-6) between the busbar CTs and the SEPAM relay. The transformer was monitored energized without load for two days. A functional test on 15 March 2026, by simulating a pressure trip signal to the RET620 relay, confirmed correct tripping of TR-A and successful automatic closing of the bus coupler, proving the ATS operated normally after the event. Keywords: Transformer Protection, RET620, Pressure Trip, Automatic Transfer Scheme, Bus Coupler, Incomer Trip, Substation Reliability, Petroleum Facility, CT Terminal Block, False Trip
Author: Mostafa, Mohamed Magdy sayed
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W7233598377
Cites:
Cited by:
Related to: