Comparative Experimental Analysis of Thermal Performance in Parallel-Flow and Counter-Flow Shell-and-Tube Heat Exchangers Under Varying Cold-Fluid Flow Rates

Year: 2026
Type: article
Abstract: Shell-and-tube heat exchangers are widely employed in industrial thermal systems because of their robustness and versatility. This study experimentally compares the thermal performance of a laboratory-scale shell-and-tube heat exchanger operated in parallel-flow and counter-flow configurations while the cold-water flow rate is varied from 1.0 to 3.0 L/min at a fixed hot-water flow rate of 3.0 L/min. Ten steady-state observations were recorded. Heat duties of both fluid streams, logarithmic mean temperature difference (LMTD), and thermal effectiveness were calculated from the measured inlet and outlet temperatures using standard energy-balance and effectiveness–NTU relations. Effectiveness decreased monotonically with increasing cold-fluid flow rate for both arrangements (from 30.8 % to 13.4 % in parallel flow and from 28.6 % to 12.2 % in counter-flow). LMTD increased modestly with cold-fluid flow rate. Relative energy-balance discrepancies between the hot-side and cold-side heat duties reached several tens of percent in some runs and are attributed primarily to heat losses to the surroundings. The results quantify the dominant influence of the capacity-rate ratio on effectiveness under the tested laboratory conditions and provide a practical data set for teaching and for validating simplified analytical models of shell-and-tube heat exchangers.