Work

Cool With It As It Comes: Data Center Cooling on Permian Produced Water

Year: 2026
Type: conference-abstract
Abstract: roduced water, with the treatment it already gets before injection, carries the heat from a data center's closed loop into a pond, and floating evaporators strip the heat from the pond. No desalination. One 250 MW campus takes 112,300 barrels a day, sends 48,100 off as vapor and returns 64,200 to the disposal well at 210,000 mg/L. Tower power is $6.2 million a year against $55.7 million to clean the same brine for the river. Graphic, 2160 px wide. Six numbered references are listed on the graphic. Capital is not included for either route. Competing interest: Resource West Inc. makes the HydraCool floating evaporator shown.
Language: English
Open Access status: green
OpenAlex ID: W7234212976
Cites:
Cited by:
Related to: 10