Work

Energy and Environmental Analysis of a Heat Recovery Ventilation System with Return-Air Evaporative Cooling in Hospital Air Handling Units

Year: 2026
Type: article
Abstract: This study investigates the energy and environmental performance of a hospital air handling unit integrated with a plate heat recovery ventilation (HRV) system and return-air evaporative cooling under hot climatic conditions. The evaporative cooling (EC) stage is applied to the return/exhaust air before the plate heat exchanger, reducing its temperature and enhancing the sensible heat recovery process. The results show that the cooling load of the conventional system reaches a maximum of 39.67 kW, while the proposed HRV+EC configuration achieves a maximum cooling capacity reduction of 18.23 kW. The annual electricity consumption decreases from approximately 17,700 to 9,600 kWh/year, corresponding to a reduction of about 46%. The associated annual CO2 emissions decrease from approximately 11 to 6 tons/year, equivalent to a reduction of approximately 45%. The results demonstrate that combining return-air evaporative cooling with heat recovery can substantially reduce cooling demand, electricity consumption, and the associated environmental impact of hospital HVAC systems operating in hot climates.
Language: English
Open Access status: diamond
OpenAlex ID: W7235477644
FWCI:
Cites:
Cited by:
Related to: 10