Work

Modeling Earth Returns and Analyzing Faults in SWER System with Heterogeneous Soils

Year: 2026
Type: article
Abstract: Single wire earth return power lines use the ground as the normal path for return current. Their operating performance and response to faults therefore depend on soil properties. Conventional models generally assume homogeneous soil, although soil resistivity can vary with depth and along the line route. This study proposes an electrical model that accounts for both types of variation. An eighty-kilometer line is divided into ten longitudinal zones, and the Martins Britto formulation is used to represent the layered soil in each zone by an equivalent complex conductivity. The self and mutual impedances are then calculated for each zone. The loop impedance is obtained by subtracting twice the mutual impedance from the sum of the two self-impedances. The Carson formulation serves as the reference, while the Deri approximation supplies the parameters for simulations in Simulink. The model represents the earth return path in heterogeneous soils and supports preliminary engineering and safety assessments. Field measurements are needed to validate the model for a specific site.
Language: English
Open Access status: diamond
OpenAlex ID: W7235910043
FWCI:
Cites: 13
Cited by:
Related to: 10