Work

MULTI-FACTOR ASSESSMENT OF CORONA LOSSES IN A 220 kV OVERHEAD TRANSMISSION LINE USING A PHYSICS-INFORMED STATISTICAL MODEL

Year: 2026
Type: article
Abstract: Corona losses in high-voltage overhead lines depend on conductor voltage and geometry, surface condition, and atmospheric density, humidity, wind, and dust. This paper presents a physics-informed statistical model for estimating corona power loss per unit line length and integrating it over an operating period. The formulation combines a corrected inception-voltage criterion, a nonlinear voltage-dependent power term, and second-order interactions among normalized environmental variables. A 220 kV L–Bessopan (L–17) line is used as the study object. Under the stated baseline conditions, the relative air-density factor is 0.891. A previously calculated mean specific corona-loss power of 0.64 kW/km corresponds to 84.83 MWh over 184.1 km and 720 h. This is a computational illustration; validation requires synchronized electrical and meteorological measurements.
Author: Islom Togaev
Language: English
Open Access status: green
OpenAlex ID: W7236235819
FWCI:
Cites:
Cited by:
Related to: 10