Work

SAP Integrated Encapsulation for Enhanced Fire Resistance of Container Frame Beams

Year: 2026
Type: article
Abstract: Rapid fire spread and the insufficient durability of conventional passive measures pose critical challenges to the fire safety of container frame structures. This study proposes an innovative active–passive synergetic fire protection system that integrates superabsorbent polymer (SAP) embedded encapsulation (passive) with full-coverage water mist spray (active). The system utilises polypropylene honeycomb panels for SAP storage and an integrated pipeline network for efficient moisture fixation and dynamic replenishment. Key flow velocity parameters for different coverage requirements were optimised via multiphysics simulations and visual tests, validating the feasibility of ‘one-time high-flow-rate filling’ and ‘alternating high/low-flow-rate’ spray schemes. Subsequently, 10 fire performance tests were conducted using a heating programme with a peak temperature similar to that of the hydrocarbon (HC) fire curve. Three spray schemes were evaluated: continuous high-flow-rate spray, one-time high-flow-rate filling, and alternating high/low-flow-rate spray. The results demonstrate that both the continuous high-flow-rate and alternating spray schemes did not reach their fire resistance limits within 60 min, with water consumptions of approximately 21.07 and 6 m3, respectively. Notably, the one-time high-flow-rate filling scheme extended the fire resistance of four-side exposed beams by over 40 min while consuming only 0.15 m3 of water. Furthermore, the dynamic distribution of SAP accumulations was predominantly governed by cross-sectional geometry and fire exposure conditions. Finally, differentiated application recommendations are proposed based on the fire resistance requirements and water resource constraints for various scenarios.
Source: Fire
Language: English
Open Access status: gold
Estimated APC paid: $2,896
OpenAlex ID: W7236292372
FWCI:
Cites: 24
Cited by:
Related to: 10