Solar-Term Architecture as a Temporal Framework for Indoor Environmental Quality: A Four-Domain Monitoring Protocol and Case Illustration from a Subtropical Adaptive-Reuse Office in Taiwan

Year: 2026
Type: article
Abstract: Solar-Term Architecture treats time as an active design variable; this article develops its measurable interpretation through the In-SENSE Lab, an adaptively reused office in Taichung, Taiwan. Continuous thermal and CO2 monitoring is combined with companion-study spot measurements of lighting and noise, indexed by the Twenty-Four Solar Terms as a culturally grounded calendar for locally measured environmental change rather than as fixed climatic labels. Term-level analysis uses 6561 laboratory hourly means across 19 Solar Terms (1 December 2025–4 September 2026). The companion study reports an annual mean predicted mean vote of −0.16, mean weekday CO2 of 465 ppm, a color-rendering index of 88–98, background noise of 26.2 dB(A), and eight of twelve months without mechanical cooling. Term statistics resolve transitions hidden by monthly aggregation: occupied-hour CO2 medians reach 565–785 ppm in adequately sampled terms; uncorrected fixed-input PMV medians move from negative in winter to near zero in summer (winter values extend beyond the ±3 scale of ISO 7730 and are read as within-case indicators); and metered daily energy separates free-running days (about 1 kWh/day) from cooling episodes (up to 117.0 kWh/day). Annual averages alone are insufficient. The principal contribution is a replicable four-domain protocol linking Solar-Term temporality with indoor environmental quality, and a minimum term-level reporting template.
Language: English
Open Access status: gold
Estimated APC paid: $2,896
OpenAlex ID: W7236671835
FWCI:
Cites: 20
Cited by:
Related to: 10