Annual Load Indicators as Quantitative Descriptors of Power System Transition: A Case Study of the Polish Power System

Year: 2026
Type: article
Abstract: The increasing share of renewable energy sources (RESs) has altered the relationship between installed generation capacity and electricity demand in the Polish Power System (PPS). This study examines changes in capacity utilization and annual load curve characteristics during the energy transition, based on operational data for 2015–2025. Four indicators were evaluated: installed capacity utilization time (Ti), utilization factor at peak load (UF), installed capacity-to-average-load ratio (CTA), and annual load factor (LF). Their relationships with RES penetration and total installed capacity were examined using linear and nonlinear regression models. Between 2015 and 2025, the RES share increased from 14.1% to 48.0%, while total installed capacity grew from 40.445 GW to 77.331 GW. Over the same period, Ti decreased by 48.7%, UF by 44.9%, and CTA increased by 94.8%. The four indicators provide complementary perspectives on changes in the operational characteristics of the PPS. Total installed capacity showed stronger statistical relationships with Ti, UF, and CTA than RES penetration, whereas neither variable adequately described variations in LF. The proposed indicator set provides a quantitative framework for assessing changes in the relationship between generation capacity and system load during the energy transition.