Abstract: Annual and regional emission factors obscure hourly and nodal variation in clean electricity availability. We developed a consumer-side carbon accounting workflow that combines hydropower dispatch, proportional-sharing electricity tracing and masked certification. In a modified IEEE 39-bus system, nodal clean electricity fractions ranged from 2.95 percent to approximately 100 percent, while three constructed industrial consumers had period-total fractions of 1.96–23.70 percent. A fixed Gaussian mask was shared among trustees and removed before release; a smaller hourly perturbation remained. Across 100 Monte Carlo runs, the released estimates had a mean absolute error of 2.200 MW and a period-total absolute error of 36.08 MWh, compared with 9.272 MW and 240.78 MWh for the tested local-noise baseline. The hybrid scheme also had a 49.24 percent mean absolute percentage error and a 9.33 percent clipping rate. These results support finer spatial attribution and lower absolute error under the selected settings, but do not establish a formal differential-privacy guarantee.