Maximize The Reliability of A Distribution System Based on Data Monitoring on Distribution Transformer Power Using The Fuzzy Decision Making Method Based on The Analytical Hierarchy Process (AHP)
Year: 2026
Type: article
Abstract: Distribution transformers are critical components in the electric power distribution system. Transformer failure can cause power outages and economic losses, so a systematic reliability evaluation method is needed. Previous studies generally evaluate reliability based on damage data parameters. The novelty of this study lies in the integration of four operating parameters (voltage, power factor, unbalance, and loading) simultaneously using the Fuzzy Decision Making method based on the Analytical Hierarchy Process. This study aims to analyze and determine the reliability ranking of three distribution transformer units based on monitoring data at Peak Load Time. The AHP weighting results show that power factor has the highest weight (0.47), followed by loading (0.27), unbalance (0.16), and voltage (0.10) with a Consistency Ratio of 0.012 (valid). The analysis results show that the East Transformer has the highest reliability index (73% - Good), the North Transformer (71% - Good), and the South Transformer (50.9% - Sufficient). The South Transformer requires priority repair due to high underload and unbalance conditions.
DOI: 10.63822/kbkf6944
Institution: Universitas Negeri Surabaya
Language: English
Subfield: Safety, Risk, Reliability and Quality
Field: Engineering
Domain: Physical Sciences
Open Access status: hybrid
OpenAlex ID: W7237348463