Work

Do Religamento Convencional À Decisão Informada: Revisão Crítica De Três Estudos Sobre Religamento Adaptativo E Self-healing Em Sistemas De Potência

Year: 2026
Type: article
Abstract: Fixed dead-time reclosing does not check whether the fault persists; smart grids allow measurement-based decisions. This work critically reviews three papers, selected purposively and non-systematically, on adaptive reclosing in transmission and self-healing in distribution, and produces a comparison matrix, a table of extracted results and a list of gaps. In the test networks of one study, the MISOCP reference solution decided in under 1 s, and the faster reinforcement learning policy served 7.9% to 18.9% less energy. The distribution studies lack field validation, and the review reports no tests of its own; integrating decision-making with protection and communication remains open.
Language: English
Open Access status: diamond
OpenAlex ID: W7237539031
FWCI:
Cites:
Cited by:
Related to: