Limiter-aware reset control of the power synchronization loop for fault recovery of grid-forming inverters
Year: 2026
Type: preprint
Abstract: Grid-forming inverters synchronize through a power synchronization loop whose damping falls as the grid becomes stronger and whose transient stability suffers when a fault drives the converter into current limiting. This paper proposes a reset controller for this loop. A constant-in-gain lead-in-phase (CgLp) element, formed by a lead filter followed by a first-order reset element, replaces the linear droop path, so that a reset at a zero crossing of the power error clears the frequency deviation accumulated during a disturbance. A limiter-aware rule adds resets on the unfiltered power error while the current limiter is active. Outside current limiting, stability of the reset loop is certified with the H β condition for short-circuit ratios from 1.5 to 50. The controller is compared with droop control, two lead compensators, and two virtual synchronous generator damping schemes, all tuned by one rule. On an averaged model it raises the critical clearing time of balanced dips by 42%-84% relative to droop control, and, together with the alternating-inertia scheme, it is the only design that rides through a 120 ms bolted dip at a short-circuit ratio of 10. A switching converter model with an LCL filter reproduces the averaged results within 0.2 percentage points of overshoot at a short-circuit ratio of 2. In a modified IEEE 9-bus system, post-fault power recovery falls from 0.73–0.84 s to 0.29 s. Frequency ramps, during which the power error keeps one sign and no reset occurs, remain a limitation.
Source: Research Square
Author: Muzeeb Khan Patan
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W7238824645
