Work

Vibration and Coil-Current Fusion for Mechanical Fault Diagnosis of High-Voltage Circuit Breaker Operating Mechanisms

Year: 2026
Type: article
Abstract: Vibration and coil-current signals provide complementary information on the mechanical condition of high-voltage circuit breaker operating mechanisms. This study experimentally evaluates a specific compact workflow using feature-level fusion on a 40.5 kV outdoor vacuum circuit breaker under normal operation, bolt loosening, opening-spring force degradation, and non-latching closure. Signal-specific preprocessing uses variational mode decomposition (VMD)-assisted wavelet soft-threshold denoising for vibration and direct wavelet soft-threshold denoising for coil current. Box dimensions of local mean decomposition (LMD) component power spectra and closing-coil current timing and amplitude descriptors are fused, reduced by principal component analysis, and classified using K-nearest neighbors. The fused model correctly identifies 117 of 120 test samples (97.50%), compared with 87.50% for vibration alone, 90.00% for current alone, and 90.83% without dimensionality reduction. These results support the selected representation for the evaluated breaker, four conditions, and reported test partition under controlled no-load operation. Validation on independent breakers and under field conditions is needed before broader application.
Source: Energies
Language: English
Open Access status: gold
Estimated APC paid: $3,137
OpenAlex ID: W7238866352
FWCI:
Cites: 23
Cited by: