High-accuracy measurement of external characteristics of new-type power-electronic loads based on a four-virtual-phasor DFT algorithm
Year: 2026
Type: preprint
Abstract: External-characteristic models of new-type power-electronic loads—data-centre rectifier supplies, battery-storage converters and fast chargers—are a prerequisite for the stability analysis of converter-dominated power systems, and both the model-driven and the data-driven modelling routes ultimately rest on the accuracy of the measured voltage and current phasors. This paper addresses the modelling bottleneck from the measurement-algorithm side: a four-virtual-phasor DFT (4VP-DFT) estimator, which analytically cancels the constant and first-order terms of the spectral-leakage-induced dynamic error and shapes an equivalent combined window that suppresses off-bin interferers, is generalized from synchrophasor measurement to the measurement of both faces of the external characteristic of a 2 MVA grid-feeding rectifier-type load. The design properties are established as three propositions with closed-form proofs, and the estimator is benchmarked against plain DFT, virtual-αβ, offset-π/3, interpolated-DFT (ipDFT) and second-order Taylor–Fourier baselines under an extended condition set (frequency offsets to ± 10 Hz, harmonic distortion up to 10% THD with 50 dB noise, out-of-band and interharmonic interference, amplitude–phase modulation and magnitude–phase steps) with Monte C arlo statistics over 200 randomized realizations. At a − 5 Hz offset the maximum phase error is 0.0095°, 37% below the best virtual-phasor baseline, and the 40 ms step response remains within the 70 ms limit; the estimator dominates every single-cycle-window baseline in the single-cycle latency class, whereas the multi-cycle baselines, although more accurate in stationary conditions, require two-to-three-cycle windows and degrade beyond ± 5 Hz. In the modelling loop, the static V–I characteristic is tracked with an RMSE of 4.69 kW (62% below the plain DFT), the wideband impedance is measured in 0.2 s windows with a mean magnitude error of 0.72% (plain DFT: 6.54%), and the impedance-based stability mar g ins reproduce the analytic ranking with a worst-case deviation of 33%. Joint identification of two drifted control parameters from the accurately measured impedance recovers the true values within 2.8% and 10.9% and reduces the model-to-data discrepancy from 55.0% to 8.73%, whereas the same procedure driven by plain-DFT measurements converges to a wrong model. The results establish phasor-measurement accuracy as the shared foundation of data-driven external-characteristic modelling, model validation and measurement-driven model correction for power-electronic loads.
Source: Research Square
Authors: Li Chen, Muyong Zhen, Feiyang Xu, Chi Xu, Min Zhang, Yu Wang
Institutions: State Grid Corporation of China (China), Southeast University
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W7238875897