Abstract: A cavity flooding system has been designed to provide long-term cooling for the Accelerator Production of Tritium targetlblanket system during an internal or external large-break loss-of-coolant accident.The cavity is flooded with water from the spent module storage pool.If no active cooling systems are available, then the water in the cavity will be heated gradually to a saturation temperature corresponding to the cavity pressure and then will be boiled off very slowly.An analysis was performed, and the results show that the natural circulation flow in the cavity during the boil-off is large enough to cool the target and blanket.I.