On-line PD measuring system for MV cables : some practical aspects and implications
Year: 2003
Type: conference-paper
Abstract: In this paper the implications of substations as the termination impedance of a medium voltage cable is studied. This impedance is not only a decisive factor in choosing optimal coupling schemes for PD sensors, but also determines which solutions are feasible for communication and synchronization between PD detection sites at both cable ends. The effective impedance resulting from a distribution transformer corresponds to typically a 1 nF capacitance for frequencies within the CENELEC A-band allowed for communication. Coupling efficiency is the main obstacle for reliable communication by means of inductive coupling, since attenuation during signal propagation is relatively low: about a factor two at 100 kHz for a 4 km paper-oil insulated three-phase belted cable. Interpretation of PD distributions depend on the eccentricity of the elliptical field within a three-phase belted cable, and thus on the location of the defect but also on the phase angle of the applied field. This results in a modification of the PD patterns as compared to off-line tests with only one phase energized.