Year: 2005
Type: conference-paper
Abstract: In this paper we analyze the experimental results for a counter flow micro heat exchanger built and tested at the Forschungszentrum Karlsruhe, by comparing them with the numerical results, using a "in house" computer code FLUTAN and the commercial code FLUENT.This counter flow micro heat exchanger consists of 6 stainless foils, four double side channels and two with channels only on one side.The thickness of the foil is 1mm and between these six foils we have five blind foils with a thickness of 0.1mm.In the cross section a micro channel is 200 μ m width and 100 μ m high.The distance between 2 channels is 100 μ m.These channels are 30mm long.Numerical studies started considering two channels, one with hot water and another with cold water, and the flow as laminar one (in cold channel the Re number varies from 404 to 1169 and in the warm channel from 894 to 3174).And because the results weren't comparable with the experiments, we moved on and we considered the flow a turbulent one using the k-ε low Re numbers model and k-ε high Reynolds number model.The conclusion was that when we considered the flow as a turbulent one, we get results comparable with the experiments.This conclusion was also verified with the commercial code FLUENT.
Institution: Karlsruhe Institute of Technology
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W840796395