Use of a General Control Simulation Program to Evaluate Hvac Control Stability
Year: 1987
Type: article
Abstract: A general process engineering simulation program for a microcomputer is used to evaluate the response of a cooling system to changes in load, set point, and controller tuning parameters to better understand the control stability of a supply air cooling system used in the Mobile Windows Thermal Test (MoWiTT) Facility.A detailed system model is built out of standard components and is used to plot the steady state performance under different operating conditions.The response of the cooling coil output depends strongly on the transport delays.For a system with a linear control valve, the process gain of the cooling coil increases rapidly as the valve flow fraction decreases.A system which is stable at mid-range is shown to become marginally unstable at the low end of the control range.The application of both an equal percentage valve and reheat are shown to improve the control response of the system under low cooling load conditions.
Authors: Xinbang Zhang, M. Warren
Language: English
Subfield: Building and Construction
Field: Engineering
Domain: Physical Sciences
Open Access status: green
Funder: U.S. Department of Energy
Awards: G1643223109, G193590374