Performance characteristics of an air-cooled steam condenser incorporating a hybrid (dry/wet) dephlegmator

Year: 2008
Type: dissertation
Abstract: This study evaluates the performance characteristics of a power plant incorporating a steam turbine and a direct air-cooled dry/wet condenser operating at different ambient temperatures. The proposed cooling system uses existing A-frame air-cooled condenser (ACC) technologyand through the introduction of a hybrid (dry/wet) dephlegmator achieves measurable enhancement in cooling performance when ambient temperatures are high.In order to determine the thermal-flow performance characteristics of the wet section of the dephlegmator, tests are conducted on an evaporative cooler.From the experimental results, correlations for the water film heat transfer coefficient, air-water mass transfer coefficient and the air-side pressure drop over a deluged tube bundle are developed.During periods of high ambient temperatures the hybrid (dry/wet) condenser operating in a wet mode can achieve the same increased turbine performance as an oversized air-cooled condenser or an air-cooled condenser with adiabatic cooling (spray cooling) of the inlet air at a considerably lower cost.For the same turbine power output the water consumed by an air-cooled condenser incorporating a hybrid (dry/wet) dephlegmator is at least 20% less than an aircooled condenser with adiabatic cooling of the inlet air.
Author: J. A. Heyns