Optimisation of a Porous Electroosmotic Pump, Used in Thermal Cooling System of Power Electronics
Year: 2007
Type: conference-paper
Abstract: The liquid cooling of electronic components is generally implemented by a mechanical pump, which requires a minimal maintenance to ensure the reliability of the device. To solve this problem, it is proposed to replace the mechanical pump by a static one, for example an electro-osmotic (EO) pump. In this paper, firstly we present the theory of the electro-osmosis phenomena, and a model of a porous EO pump. Then an optimization of a porous EO pump made of sintered silica is presented. It was found that for any porous EO pump the optimum operating point of the pump is determined by controlling the diameter of the effective pore radius of the porous silica and the Debye length. Using deionised (DI) water as pumping liquid, the EO pump generates 13.6 ml/min and 2 kPa at 150 V applied voltage. The power consumed by the pump is less than 0.4 W. The EO pump works without any bubbles in the hydraulic circuit. This design can be used to cool 47 W of power generated by the power components with a forced convection without evaporation and 270 W with evaporation.
Institutions: Institut polytechnique de Grenoble, University of Notre Dame
Language: English
Subfield: Biomedical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W2016333880