Work

Effect of wave form upon the iron losses in transformers

Year: 1908
Type: article
Abstract: Effect of Wave Form upon Transfor^ners.479 We assume the iron losses in the transformer to be represented by the modified form of the Steinmetz formula, W^W^^W^ The induced voltage in the primary winding of a transformer differs from the applied voltage by the amount of the ohmic drop, or dif- ference of potential due to resistance.As the ohmic drop is small, and as consideration of it introduces difficulties, we shall consider only the induced voltage.Commercial voltmeters measure the effective value of the voltage.We assume consequently that with different wave forms the effective value of the induced voltage is the quantity kept constant.This approximates closely to practical conditions.Since the induced voltage depends upon the rate of change of the magnetic flux, its average value at a definite frequency is propor- tional to B^and its effective value to/B, If the effective value be kept constant, the term in the above formula representing eddy currents will be constant at any definite frequency.The only change in JV^iW arise from an alteration in B^which must accompany any alteration iny.W-W^Wu-IV, H-'^'^H .w, w. '-<s,-)4(ir-]If B-Bq be small in comparison with B^^this may be written B-B.1.6 q- B.If B and q be known, the change in power may be calculated.q may be determined approximately by runs at two frequencies, using sine waves and voltages proportional to the frequencies.One frequency n^and voltage should be those used with the varying 22832-08
Author: M. G. Lloyd
Language: English
Open Access status: bronze
OpenAlex ID: W2322342136
FWCI:
Cites:
Cited by: 1
Related to: 9