Abstract: This experiment analyzes the tendency of fire detection through combustion products generated during UL 268 wood flame fires and smoldering tests. Fire detection tendency was measured using a particle matter sencor (PMS), combustion gas analyzer (CGA), and gas analyzer (GA). The combustion products were matched and analyzed at 5 %/m (non-operation), 10 %/m, and 15 %/m of the smoke sensitivity measured by the smoke detector. In the case of wood flaming fire, PMS PM 10, CGA CO, SO2, GA HCHO, and TVOC, the trend was observed because of the continuous increase in the measured value according to the smoke generation. In the case of smoldering, PM 10, CO, and HCHO were adaptable to the tendency to be observed. Finally, in the case of wood fire accompanied by flame fire and smoldering to PM 10, CO and HCHO were considered to be the optimal fire detection factors.