Year: 2015
Type: article
Abstract: The costs of offshore maintenance operations put high reliability-requirements on offshore equipment for ocean energy, especially on submerged ones. Thermal management is thus essential in the design of the prototypes of a marine substation, developed at Uppsala University, for grid interface of wave power parks. The cooling system itself should be efficient as well as reliable. Therefore, the feasibility of a completely passive cooling strategy was evaluated. The studied substation includes various power components, which dissipate heat and are installed in one pressurized vessel. Thermal cross-coupling was investigated with 3-D submodels and a thermal network model. An electric circuit was coupled to determine the rated power of the substation. The results depend mainly on the dc-voltage, the seawater temperature, and the thermal contact between the components and the hull.
Authors: Antoine Baudoin, Cecilia Bostrom, Mats Leijon
Institution: Uppsala University
Language: English
Topic: Wave and Wind Energy Systems
Subfield: Ocean Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: hybrid
Estimated APC paid: $2,645
Funders: Energimyndigheten, Uppsala Universitet
OpenAlex ID: W658787703