Post-fault Transient Enhancement Based on Adaptive Power-Angle Resetting for Grid-forming Inverter With Current Limiting Considering Phase Jumping Along With Fault Clearance

Year: 2026
Type: article
Abstract: The increasing penetration of inverter-based renewable energy systems requires grid-forming (GFM) inverters to maintain stable operation under fault conditions. However, their transient stability is significantly challenged when current-limiting mechanisms are activated, particularly when the power angle exceeds the unstable equilibrium point (UEP). To address this issue, an adaptive power-angle resetting (APAR) strategy is proposed to enhance post-fault recovery performance without relying on grid impedance information. The proposed method decouples the power-angle dynamics from the conventional power synchronous loop(PSL), enabling direct regulation of the power angle through an integrator resetting mechanism. Furthermore, the operating region is partitioned according to system states, and an adaptive adjustment scheme is developed to regulate the power angle under different fault conditions. And the Lyapunov energy-based stability analysis demonstrated that this proposed method can drive the system state to converge to stable operation point. Compared with existing approaches, the proposed strategy effectively suppresses post-fault oscillations, accelerates transient recovery, and maintains robustness under grid phase jumps. The effectiveness of the proposed method is validated through both simulation and experimental results.
Language: English
Open Access status: hybrid
Estimated APC paid: $2,645
OpenAlex ID: W7208737697
FWCI:
Cites:
Cited by:
Related to: 10