Investigation of Differential Protection Failure During an Internal Single-Line-to-Ground Fault in a Dyn-Connected Transformer
Year: 2026
Type: conference-paper
Abstract: This paper investigates a critical protection failure at a primary substation where a single-line-to-ground fault within the differential zone of a 20/26 MVA, 33/11 kV Dyn1 transformer was not detected by the installed electromechanical differential relay. The fault, initiated on the transformer's secondary side, was sustained because current was supplied through a zig-zag grounding transformer, resulting in tripping of only the secondary breaker while the transformer remained energized. This condition created severe safety hazards, including dangerous touch potentials that nearly led to operator electrocution. Through system modeling and protection analysis, the study identifies the root causes-limited relay sensitivity, inappropriate CT ratio selection, and deficiencies in the grounding protection philosophy. Corrective measures, including deployment of microprocessor-based differential relays, sensitive residual ground fault elements, and revised tripping logic, are proposed. The findings underscore the importance of modern protection schemes and provide lessons for utilities managing legacy electromechanical systems.
Institution: Ghana Standards Authority
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: hybrid
OpenAlex ID: W7220699080
