Design space analysis of nuclear-absorption chiller systems for data center applications

Year: 2026
Type: article
Abstract: Summary: Rising data center electricity demand drives interest in co-located nuclear power. Here, we evaluate direct thermal cooling for nuclear-powered data centers, coupling four reactor designs—PWR, SFR, HTGR, and VHTR—to LiBr-H 2 O absorption chillers. Performance is quantified using the peak IT load-to-reactor capacity ratio (PIR). Two modeling frameworks provide screening-to-deployment strategies, where rapid assessment identifies the thermodynamic opportunity and detailed thermal modeling determines how much of that opportunity remains under specific balance-of-plant (BOP) constraints. Rapid assessment establishes an upper-bound showing absorption cooling achieves 6.5%–16% higher PIR than electric chiller baselines. Thermal modeling agreement with rapid assessment depends on extraction-temperature matching. Deviations are small in well-aligned cases, reaching 0%–3% for selected double- and triple-effect configurations, but increase to 19% for single-effect chillers, signaling the value of targeted BOP redesign. Sensitivity analyses of transport temperature drops and varying sink conditions confirm minimal impact on these relative cooling advantages.